1

Medium

Why is ammonia (NH₃) considered a toxic refrigerant?


It does not react with water, which makes it difficult to neutralise
It is flammable and can form explosive mixtures with air
It is highly irritating to the respiratory tract and toxic if inhaled
It is colourless and odourless, so it is difficult to detect

2

Difficult

What is the main difference between a dry evaporator and a flooded evaporator?


A dry evaporator does not require an expansion valve, whereas a flooded one does
A dry evaporator allows the entire refrigerant to evaporate in the pipe upstream of the compressor; in a flooded evaporator, part of the refrigerant remains in a liquid state within the evaporator
A dry evaporator has a lower operating pressure than a flooded one
A dry evaporator is filled with refrigerant liquid, whilst a flooded evaporator is filled with gas

3

Difficult

What is the typical pressure in deep-freezing systems (below −40 °C) for an evaporator in a system using R717?


Atmospheric pressure, approximately 1 bar
Positive pressure, in the range of 5–10 bar
A pressure varying between 10 and 20 bar
Negative pressure (vacuum), below 0 bar

4

Difficult

Why are PFAS substances formed as a result of the decomposition of certain F-gases problematic?


They cause rapid cooling of the atmosphere
They are climate-neutral
They are persistent, accumulate in the environment and may be toxic
They are readily biodegradable, so they only pollute the environment for a short time

5

Difficult

What is the basic requirement when charging a system with R717 (NH₃)?


Charging can be carried out without personal protective equipment
Charging must only take place at temperatures below 0°C
Charging should take place in a well-ventilated area using appropriate personal protective equipment
NH₃ can be charged together with air

6

Difficult

How should oil be handled in systems using R717?


The oil should be checked regularly and any excess removed from the lower parts of the units to prevent reduced heat transfer and leaks
Oil has no effect on the system’s operation
The oil does not require any monitoring
Oil can be mixed with any refrigerant

7

Difficult

What is the correct procedure for recovering R717 from a system?


The refrigerant can be drained into the sewer system
The refrigerant must be recovered into suitable, leak-proof tanks designed for NH₃
Recovery is not required
The gas can be released into the atmosphere

8

Difficult

How should R717 (NH₃) be stored?


Near heat sources
In any open containers
In unmarked plastic containers
In sealed, labelled containers, in a cool and well-ventilated place

9

Difficult

What should be done in the event of R717 contamination?


Continue to use without restriction
The refrigerant must be purified or sent for disposal in accordance with regulations
Add water to dilute it
Release into the atmosphere

10

Difficult

What is the main hazard associated with an R717 leak during maintenance work?


No risk whatsoever
Toxic to humans and may cause chemical burns
Damage to electrical equipment only
Increased cooling efficiency

11

Difficult

What action should be taken if an NH₃ leak is detected?


Close your eyes and carry on working
Increase the pressure in the system
Ignore it and carry on working
Evacuate personnel immediately and remove the source of the leak, if it is safe to do so

12

Difficult

What role do scrubbers play in NH₃ systems?


They increase the pressure in the system
Neutralises ammonia through absorption in a liquid (e.g. water)
They store the refrigerant
They are used to measure temperature

13

Difficult

How should the system be prepared before filling with R717?


There is no need to check it
The pressure must be increased above the standard level
Simply start it up
Check for leaks, remove air and moisture, and create a vacuum

14

Difficult

What are the transport requirements for R717?


Must be transported in suitable, labelled containers in accordance with ADR regulations
Transport is not subject to regulations
It can be transported in open containers
It can be transported without labelling

15

Difficult

What personal protective equipment is required when working with NH₃?


Only a safety helmet
Workwear only
No requirements
Safety goggles, gloves and respiratory protective equipment

16

Difficult

Which statement best describes the behaviour of R717 and mineral compressor oil?


In an R717 system, a return oil line cannot be used because the oil is too hot
R717 does not mix with compressor oil, so the oil remains in the system on the high-pressure side as a layer above the R717
R717 mixes very well with compressor oil and easily returns to the compressor
R717 does not mix with compressor oil, so the oil remains in the system on the low-pressure side as a layer beneath the R717

17

Difficult

Which system may require manual oil recovery?


Secondary system using R744
R744 cascade system
An R717 system
Supercritical ‘booster’ system using R744

18

Difficult

Which refrigerant is lighter than air?


R717
R744
R1234ze
R1270

19

Difficult

R717 is highly corrosive to


stainless steel
titanium
aluminium
copper

20

Difficult

What is the effect of repeatedly opening the relief valve?


The valve remains fully open continuously
The relief pressure drops
The valve will not open
The relief pressure rises

21

Difficult

What is the relationship between the pressure (P) and temperature (T) of nitrogen at the start (1) and end (2) of the leak test?


P2 = T2/(P1 × T1)
P2 = (P1 × T1)/T2
P2 = T1/(P1 × T2)
P2 = (P1 × T2)/T1

22

Difficult

What is the recommended alarm level for fixed leak detection systems for R717?


500,000 ppm
500 ppm
5,000 ppm
50,000 ppm

23

Difficult

Why are compressors with a separate electric motor most commonly used in R717 (NH₃) refrigeration systems?


Because NH₃ reacts with the motor windings and hermetic compressors are not used
To increase the amount of refrigerant in the system
Because compressors with a separate motor are cheaper
To reduce the condensing pressure

24

Difficult

Which type of compressor is most commonly used in large ammonia systems?


Rotary vane compressor
Hermetic scroll
A reciprocating or screw compressor
Diaphragm compressor

25

Difficult

How is the capacity of a piston compressor regulated in NH₃ systems?


Solely by adjusting the oil volume
By reducing the refrigerant charge
By increasing the condensing pressure
By unloading the cylinders or changing the rotational speed

26

Difficult

How is the capacity of a screw compressor most commonly controlled?


By closing the suction valve
By adjusting the oil level
By using a slide valve
By changing the type of oil

27

Difficult

When is two-stage compression used in NH₃ systems?


At very low vapour pressures and high pressure differentials
Only with water-cooled condensers
Exclusively in small systems
At small temperature differences

28

Difficult

What is the advantage of two-stage compression over single-stage compression?


Higher efficiency and lower discharge temperature
No need for a separator
Higher energy consumption
Lower efficiency

29

Difficult

How does an evaporative condenser used in NH₃ systems work?


It does not require a water supply
It transfers heat only to the air
Operates without a fan
It utilises the evaporation of water to increase cooling efficiency

30

Difficult

What is the function of the liquid separator in an NH₃ system?


It separates oil from the refrigerant
Regulates the condensing pressure
Increases the discharge temperature
It prevents liquid from entering the compressor

31

Difficult

What is the purpose of monitoring the liquid level in the separator?


To reduce the condensing temperature
To control the condenser fan
To maintain the correct refrigerant level and prevent the compressor from flooding
To increase the oil volume

32

Difficult

What is the role of the float switch in NH₃ systems?


It is used to detect leaks
It controls the fan’s operation
It monitors the liquid level in the tank or separator
It regulates the condensation temperature

33

Difficult

What is a thermosiphon in NH₃ systems?


A defrosting device
A type of evaporator
An oil circulation system utilising differences in pressure and temperature
A type of safety valve

34

Difficult

Why are oils that are immiscible with the refrigerant used in NH₃ systems?


Because NH₃ does not mix with most compressor oils
To increase the amount of refrigerant
To reduce the pressure
Because the oil mixes only with water

35

Difficult

What is the main function of an oil separator in NH₃ systems?


Removing moisture from the system
To lower the condensation temperature
To increase fan efficiency
To separate the oil from the refrigerant and return the oil to the compressor

36

Difficult

Which NH₃ system features direct evaporation of the refrigerant in the evaporator?


Direct expansion (DX) system
Glycol system
Thermosiphon system
Indirect system

37

Difficult

What is the characteristic feature of a flooded evaporator system?


The evaporator is filled exclusively with vapour
No level control is required
The evaporator contains a large amount of liquid, which improves heat transfer
No separator is used

38

Difficult

What is the main difference between a direct and an indirect system?


In an indirect system, NH₃ cools an intermediate medium (e.g. glycol), which in turn cools the load
In an indirect system, no compressor is used
In an indirect system, NH₃ flows directly into the space being cooled
In a direct system, there is no evaporator